Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 29, 2017, 10:03 AM
  • 08 0036_08 0035 _29122017_022059.mp4

Date
12/29/2017
W/O
679386
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00038
Time
2:03 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5299
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_679386_TV08115_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
08 0036
Downstream MH
08 0035
Dir. of Survey
Downstream
Length Surveyed
319.8 ft.
Total Length
319.8 ft.
Structural Index
2
Structural Quick
4227
Structural Rating
22
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
22
Pipe schematic from manhole 08 0036 to 08 0035
MH: 08 0036MH: 08 0035downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 00360 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area28.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"30 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES56.1 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES, Start61.1 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES, Finish80.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"126.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"182.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"182.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start190.9 ft. FM - Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES, Start197.4 ft. FM - Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES, Finish207.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish229.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"272.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"289.3 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES319.8 ft. AMH - Downstream Manhole, Survey Ends - 08 0035

Observation photos (5)

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    30 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES, Start

    56.1 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    182.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES, Start

    190.9 ft. - Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    289.3 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
207.9CL
229.2TFC
289.3CL
61.1FM
80.7TFC
190.9FM
272.2TFC
0AMH08 0036
0MWL
197.4FM
28.6TFC
56.1FM
126.7TFC
182.5TFC
319.8AMH08 0035
182.5CL
0MWM
30CL

Properties (4)

additional_info
SC346773
custom_field_two
2
customer
LACSD
datetime
2017-12-29T02:03:21-08:00