Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 3, 2017, 10:35 AM
  • 02 1678_02 1677_03072017_034939.mp4

Date
07/03/2017
W/O
613355
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00289
PipeID
P18835
Time
3:35 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3978-SC342141
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
MONTEREY PARK
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_613355_TV02105_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1678
Downstream MH
02 1677
Dir. of Survey
Downstream
Length Surveyed
327.5 ft.
Total Length
327.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 1678 to 02 1677
MH: 02 1678MH: 02 1677downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 16780 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start35.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"87 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"91.1 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"139.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"191.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"235.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"287.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"290.2 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"325.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish327.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1677

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
35.4TFC
191.3TFC
287.3TFC
325.7DAGS
235.2TFC
290.2TB
327.5AMH02 1677
0AMH02 1678
0MWL
87TFC
91.1TB
139.5TFC
2.6DAGS
0MWM

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2017-07-03T03:35:13-07:00