Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 5, 2017, 12:48 PM
  • 02 1672_02 1671_05072017_055833.mp4

Date
07/05/2017
W/O
613355
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00289
PipeID
P18828
Time
5:48 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3979-SC342142
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
MONTEREY PARK
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_613355_TV02105_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1672
Downstream MH
02 1671
Dir. of Survey
Downstream
Length Surveyed
124.5 ft.
Total Length
124.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 02 1672 to 02 1671
MH: 02 1672MH: 02 1671downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 16723.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"7.6 ft. RML - Roots Medium Lateral, at 12 o'clock, 20 %, within 8 inches of joint: YES43 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"52.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"86.7 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"117.2 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"122.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish124.5 ft. AMH - Upstream Manhole, Survey Ends - 02 1671

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
43TFC
0MWL
3.3DAGS
122.1DAGS
117.2TB
7.6TB
0MWM
7.6RML
86.7TB
124.5AMH02 1671
0AMH02 1672
52.2TB

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2017-07-05T05:48:51-07:00