- Date
- 07/11/2018
- W/O
- 711942
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z01180
- PipeID
- P01116
- Time
- 11:52 PM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K5773
- Sewer Name
- G JOINT OUTFALL G - UNIT 8
- City
- SOUTH GATE
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- WO_711942_TV01122_JUL2018
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- G 0212
- Downstream MH
- G 0211
- Dir. of Survey
- Downstream
- Length Surveyed
- 337.7 ft.
- Total Length
- 337.7 ft.
- Structural Index
- 3
- Structural Quick
- 3J22
- Structural Rating
- 169
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 169
Pipe schematic from manhole G 0212 to G 0211 Observation photos (5)

3.1 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

10.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

18.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

26.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

200.8 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start