Section#10_G 0114_G 0113__7252018__ I0040.mp4
0 ft. - General Observation - MAG COAT 30% START
0 ft. - General Observation - 95% MISSING TILES 10:00 TO 2:00 START
2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING CONCRETE
2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG
6.4 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - LONG & CIRCUM REBAR
13 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR
42.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR
59.4 ft. - General Observation - 100% MISSING TILES START
73.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN MISSING
78.6 ft. - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM REBAR
94.6 ft. - General Observation - PARTIAL ROW REMAINING TILES
127.8 ft. - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR
| Distance | Code | Observation |
|---|---|---|
| 290.1 | MGO | MH CONN 9:00 ACTIVE |
| 290.6 | AMH | 4:20AM |
| 152.8 | MGO | 2 ROWS TILES REMAINING |
| 112.9 | MGO | FEW REMAINING TILES |
| 0 | MWL | — |
| 2 | SSS | SWOLLEN BLISTERING CONCRETE |
| 290.1 | MGO | MH CONN 3:00 ACTIVE |
| 0 | AMH | 3:40AM |
| 290.1 | SAM | SEVERE AGG |
| 0 | MGO | MAG COAT 30% START |
| 6.4 | SRC | LONG & CIRCUM REBAR |
| 9.5 | SRC | LONG & CIRCUM REBAR CORRODED & MISSING |
| 290.1 | SSS | SWOLLEN BLISTERING CONCRETE |
| 252.8 | MGO | 2 ROWS REMAINING TILES |
| 94.6 | MGO | PARTIAL ROW REMAINING TILES |
| 204.4 | MGO | FEW REMAINING TILES |
| 127.8 | SRC | BROKEN MISSING REBAR |
| 73.2 | SRC | CIRCUM REBAR BROKEN MISSING |
| 59.4 | MGO | 100% MISSING TILES START |
| 290.1 | MGO | MAG COAT 30% FINISH |
| 177.5 | MGO | FEW REMAINING TILES |
| 290.1 | MGO | 100% MISSING TILES FINISH |
| 290.1 | SRC | LONG & CIRCUM REBAR CORRODED & MISSING |
| 42.9 | SRC | CORRODED MISSING REBAR |
| 78.6 | SRC | BROKEN CIRCUM REBAR |
| 0 | MGO | 95% MISSING TILES 10:00 TO 2:00 START |
| 13 | SRC | LONG & CIRCUM REBAR |
| 0 | MWM | — |
| 2 | SAM | SEVERE AGG |