Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2018, 08:35 AM
  • Section#9_G 0115_G 0114__7252018__ I0037.mp4

Date
07/25/2018
W/O
0712087
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P01442
Time
1:35 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0037
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Capital Improvement Program Assesment
Project
20180723MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0115
Downstream MH
G 0114
Dir. of Survey
Downstream
Length Surveyed
302.9 ft.
Total Length
302.9 ft.
Structural Index
3
Structural Quick
5B4K
Structural Rating
434
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
439
Pipe schematic from manhole G 0115 to G 0114
MH: G 0115MH: G 0114downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:20AM0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. MWL - Water Level, 70 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 30% START2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING CONCRETE START2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - TILES 20% IN PLACE 10:00 TO 2:0024.4 ft. MGO - General Observation - 95% MISSING TILES START37.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - CORRODD & MISSING46.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish - CURCUM REBAR CORRODED & MISSING56 ft. SAM - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG--UNUSAL DEEP CORRISIN57.3 ft. SMW - Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: NO - POSSIBLE SOIL VISIBLE57.3 ft. SMW - Surface Missing Wall, from 12 to 02 o'clock, within 8 inches of joint: NO - POSSIBLE SOIL VISIBLE65.2 ft. SRC - Surface Reinforcement Corroded, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR CORRODED & MISSING72.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, - CORRODED & MISSING89 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR108 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR154.4 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR189.8 ft. SRC - Surface Reinforcement Corroded, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR247.7 ft. SRC - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN283.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 01 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM REBAR296.1 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR BROKEN & MISSING302.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR CORRODED & MISSING302.2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SWOLLEN & BLISTERING CONCRETE302.2 ft. MGO - General Observation - MAG COAT 30% FINISH302.2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG302.2 ft. MGO - General Observation - MISSING TILES 95% FINISH302.9 ft. AMH - Downstream Manhole, Survey Ends - 3:20AM

Observation photos (18)

  • General Observation - MAG COAT 30% START

    2 ft. - General Observation - MAG COAT 30% START

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING CONCRETE START

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING CONCRETE START

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - TILES 20% IN PLACE 10:00 TO 2:00

    2 ft. - General Observation - TILES 20% IN PLACE 10:00 TO 2:00

  • General Observation - 95% MISSING TILES START

    24.4 ft. - General Observation - 95% MISSING TILES START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - CORRODD & MISSING

    37.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - CORRODD & MISSING

  • Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG--UNUSAL DEEP CORRISIN

    56 ft. - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG--UNUSAL DEEP CORRISIN

  • Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: NO - POSSIBLE SOIL VISIBLE

    57.3 ft. - Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: NO - POSSIBLE SOIL VISIBLE

  • Surface Missing Wall, from 12 to 02 o'clock, within 8 inches of joint: NO - POSSIBLE SOIL VISIBLE

    57.3 ft. - Surface Missing Wall, from 12 to 02 o'clock, within 8 inches of joint: NO - POSSIBLE SOIL VISIBLE

  • Surface Reinforcement Corroded, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR CORRODED & MISSING

    65.2 ft. - Surface Reinforcement Corroded, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR CORRODED & MISSING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES,  - CORRODED & MISSING

    72.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, - CORRODED & MISSING

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    89 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    108 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    154.4 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    189.8 ft. - Surface Reinforcement Corroded, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN

    247.7 ft. - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN

  • Surface Reinforcement Corroded, from 10 to 01 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM REBAR

    283.3 ft. - Surface Reinforcement Corroded, from 10 to 01 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR BROKEN & MISSING

    296.1 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR BROKEN & MISSING

Observations (28)

DistanceCodeObservation
302.2SRCCIRCUM REBAR CORRODED & MISSING
154.4SRVCIRCUM REBAR
247.7SRCCIRCUM REBAR BROKEN
302.2SSSSWOLLEN & BLISTERING CONCRETE
56SAMSEVERE AGG--UNUSAL DEEP CORRISIN
0AMH2:20AM
46.9SRCCURCUM REBAR CORRODED & MISSING
2MGOMAG COAT 30% START
108SRVCIRCUM REBAR
57.3SMWPOSSIBLE SOIL VISIBLE
2SSSSWOLLEN BLISTERING CONCRETE START
37.3SRCCORRODD & MISSING
2SAMSEVERE AGG
302.2MGOMAG COAT 30% FINISH
2MGOTILES 20% IN PLACE 10:00 TO 2:00
89SRVCIRCUM REBAR
302.2SAMSEVERE AGG
0MWM
57.3SMWPOSSIBLE SOIL VISIBLE
296.1SRCCIRCUM REBAR BROKEN & MISSING
283.3SRCBROKEN CIRCUM REBAR
302.2MGOMISSING TILES 95% FINISH
65.2SRCCIRCUM REBAR CORRODED & MISSING
302.9AMH3:20AM
72.3SRCCORRODED & MISSING
189.8SRCCIRCUM REBAR
24.4MGO95% MISSING TILES START
0MWL

Properties (4)

custom_field_three
CORRODED & MISSING REBAR-1 AREA POSSIBLE SOIL VISI
custom_field_two
1
customer
LACSD
datetime
2018-07-25T01:35:35-07:00