Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2018, 08:54 AM
  • Section#12_G 0086_G 0016__7252018__ I0040.mp4

Date
07/25/2018
W/O
0712087
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P02220
Time
1:54 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0040
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Capital Improvement Program Assesment
Project
20180723MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0086
Downstream MH
G 0016
Dir. of Survey
Downstream
Length Surveyed
8.9 ft.
Total Length
8.9 ft.
Structural Index
5
Structural Quick
5141
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
9
Pipe schematic from manhole G 0086 to G 0016
MH: G 0086MH: G 0016downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:45AM0 ft. MGO - General Observation - MH CONN 3:00 ACTIVE LARGE IN COMING1 ft. MGO - General Observation - SECTION OF PIPE APPOX 2' LONG2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, - SEVERE AGG8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR8.5 ft. MGO - General Observation - CORRODED REBAR ROOF OF STRUCTURE MH G168.9 ft. AMH - Downstream Manhole, Survey Ends - 6:00AM

Observation photos (3)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES,  - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • General Observation - CORRODED REBAR ROOF OF STRUCTURE MH G16

    8.5 ft. - General Observation - CORRODED REBAR ROOF OF STRUCTURE MH G16

Observations (9)

DistanceCodeObservation
8.5MGOCORRODED REBAR ROOF OF STRUCTURE MH G16
8SRCLONG & CIRCUM REBAR
0MWM
0MWL
1MGOSECTION OF PIPE APPOX 2' LONG
0AMH5:45AM
0MGOMH CONN 3:00 ACTIVE LARGE IN COMING
8.9AMH6:00AM
2SAMSEVERE AGG

Properties (4)

custom_field_three
LONG & CIRCUM REBAR BROKEN & MISSING
custom_field_two
2
customer
LACSD
datetime
2018-07-25T01:54:43-07:00