Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 25, 2018, 09:49 AM
  • B 0368_B 0367 _25062018_025929.mp4

Date
06/25/2018
W/O
712401
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00091
PipeID
P08880
Time
2:49 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5704
Sewer Name
B JOINT OUTFALL B - UNIT 5A
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
10
Purpose
Routine Assessment
Project
WO_712401_TV15051_JUL2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
B 0368
Downstream MH
B 0367
Dir. of Survey
Downstream
Length Surveyed
243.9 ft.
Total Length
243.9 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole B 0368 to B 0367
MH: B 0368MH: B 0367downstream0 ft. MGO - General Observation - CAPPED CONNECTION AT 3 O' CLOCK AT MH0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 03680 ft. MGO - General Observation - CAPPED CONNECTION AT 9 O' CLOCK AT2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start108.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"117.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start117.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish243.9 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH243.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish243.9 ft. AMH - Downstream Manhole, Survey Ends - B 0367243.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    117.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MGOCAPPED CONNECTION AT 3 O' CLOCK AT MH
243.9MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
0MWL
243.9SSS
2.6SAV
243.9AMHB 0367
117.1SAP
0MWM
0AMHB 0368
2.6SSS
108.6TF
243.9SAP
117.1SAV
0MGOCAPPED CONNECTION AT 9 O' CLOCK AT

Properties (4)

additional_info
SC359662
custom_field_two
3
customer
LACSD
datetime
2018-06-25T02:49:58-07:00