Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 27, 2018, 06:12 AM
  • 32 0060_32 0059 _26062018_232612.mp4

Date
06/26/2018
W/O
712244
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00886
PipeID
P19824
Time
11:12 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5752
Sewer Name
32 CASTAIC TRUNK
City
CASTAIC
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
01
Purpose
Routine Assessment
Project
WO_712244_TV32012_JUL2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0060
Downstream MH
32 0059
Dir. of Survey
Downstream
Length Surveyed
278.4 ft.
Total Length
278.4 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2J00
O&M Rating
112
Overall Index
2
Overall Quick
Overall Rating
114
Pipe schematic from manhole 32 0060 to 32 0059
MH: 32 0060MH: 32 0059downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 0060, ABANDONED MH0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 25 %of cross sectional area265.1 ft. CS - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES278.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish278.4 ft. AMH - Downstream Manhole, Survey Ends - 32 0059

Observation photos (3)

  • Upstream Manhole, Survey Begins - 32 0060, ABANDONED MH

    0 ft. - Upstream Manhole, Survey Begins - 32 0060, ABANDONED MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

    265.1 ft. - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
0MWL
0AMH32 0060, ABANDONED MH
0DAGS
278.4DAGS
265.1CS
0MWM
278.4AMH32 0059

Properties (5)

additional_info
SC359718
custom_field_two
4
customer
LACSD
datetime
2018-06-26T23:12:47-07:00
year_laid
27282