Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2018, 06:39 AM
  • 02 1723_02 1722_28062018_001146.mp4

Date
06/27/2018
W/O
711968
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00289
PipeID
P18887
Time
11:39 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5807
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
MONTEREY PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
07
Purpose
Routine Assessment
Project
WO_711968_TV02245_JUL2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1723
Downstream MH
02 1722
Dir. of Survey
Downstream
Length Surveyed
365.2 ft.
Total Length
365.2 ft.
Structural Index
3
Structural Quick
4231
Structural Rating
19
O&M Index
3
O&M Quick
4131
O&M Rating
15
Overall Index
3
Overall Quick
Overall Rating
34
Pipe schematic from manhole 02 1723 to 02 1722
MH: 02 1723MH: 02 1722downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MCU - Camera Underwater, Start0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 17230 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH19.5 ft. MCU - Camera Underwater, Finish19.5 ft. FH2 - Fracture Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES26.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start76 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"117.2 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES123.6 ft. IS - Infiltration Stain, from 07 to 09 o'clock, within 8 inches of joint: YES123.6 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES129.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"129.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 04 o'clock, , within 8 inches of joint: YES147.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"235.6 ft. IS - Infiltration Stain, from 06 to 09 o'clock, within 8 inches of joint: YES241 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 12 o'clock, , within 8 inches of joint: NO241 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"282.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: NO286.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"297.9 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES, Start305.3 ft. CH2 - Crack Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES, Start305.3 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES, Finish319.4 ft. CS - Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES338.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: NO353.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"355.7 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start359.7 ft. CH2 - Crack Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES, Finish364.3 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish364.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish364.3 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH365.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1722

Observation photos (13)

  • Fracture Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES

    19.5 ft. - Fracture Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    26.7 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    117.2 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 07 to 09 o'clock, within 8 inches of joint: YES

    123.6 ft. - Infiltration Stain, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    123.6 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 04 o'clock,  , within 8 inches of joint: YES

    129.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 04 o'clock, , within 8 inches of joint: YES

  • Infiltration Stain, from 06 to 09 o'clock, within 8 inches of joint: YES

    235.6 ft. - Infiltration Stain, from 06 to 09 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 12 o'clock,  , within 8 inches of joint: NO

    241 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 12 o'clock, , within 8 inches of joint: NO

  • Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock,  , within 8 inches of joint: NO

    282.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: NO

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES, Start

    297.9 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES, Start

    305.3 ft. - Crack Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES

    319.4 ft. - Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: NO

    338.5 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: NO

Observations (32)

DistanceCodeObservation
241DAE
241TF
355.7DSC
364.3DSC
117.2CL
319.4CS
19.5MCU
129.1TF
26.7DAGS
76TF
235.6IS
282.9DAGS
338.5FL
297.9CS
305.3CH2
129.1DAE
0MWL
0MCU
286.1TFA
0MWM
353.3TFA
0AMH02 1723
364.3DAGS
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
147.6TF
123.6IS
359.7CH2
305.3CS
364.3MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
123.6CL
365.2AMH02 1722
19.5FH2

Properties (4)

additional_info
SC359531
custom_field_two
3
customer
LACSD
datetime
2018-06-27T23:39:08-07:00