Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2018, 10:13 AM
  • 18 0925_18 0924 _28062018_032255.mp4

Date
06/28/2018
W/O
711900
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00700
PipeID
P14773
Time
3:13 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5758
Sewer Name
18 SCOTT AVENUE TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_711900_TV18047_JUL2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0925
Downstream MH
18 0924
Dir. of Survey
Downstream
Length Surveyed
245.8 ft.
Total Length
245.8 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
141
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
141
Pipe schematic from manhole 18 0925 to 18 0924
MH: 18 0925MH: 18 0924downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 09250 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH9.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start65.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"142.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"145.3 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"225.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"245.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish245.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0924

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MGOCONNECTION AT MH 3 O'CLOCK
225.7TFC
9.5CM
0MWL
245.8CM
0MWM
0AMH18 0925
142.3TFC
0MGOCAPPED LATERAL 9 O'CLOCK @ MH
65.7TFC
245.8AMH18 0924
145.3TB

Properties (4)

additional_info
SC359667
custom_field_two
3
customer
LACSD
datetime
2018-06-28T03:13:02-07:00