Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 2, 2018, 09:33 AM
  • 17 0096_17 0095 _02072018_031214.mp4

Date
07/02/2018
W/O
712454
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00669
PipeID
P13814
Time
2:33 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5856
Sewer Name
17 LINCOLN AVENUE TRUNK
City
ALTADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
01
Purpose
Routine Assessment
Project
WO_712454_TV17002_JUL2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
17 0096
Downstream MH
17 0095
Dir. of Survey
Downstream
Length Surveyed
347.2 ft.
Total Length
347.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 17 0096 to 17 0095
MH: 17 0096MH: 17 0095downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 17 00960 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start26 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"123.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"256.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"324.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"344.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish347.2 ft. AMH - Downstream Manhole, Survey Ends - 17 0095

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
344.8DAGS
26TFC
0MWL
2DAGS
347.2AMH17 0095
0AMH17 0096
123.7TFA
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWM
256.2TFA
324.6TFC

Properties (4)

additional_info
SC359722
custom_field_two
4
customer
LACSD
datetime
2018-07-02T02:33:28-07:00