Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 3, 2018, 10:41 AM
  • 02 0886_02 0885 _03072018_040805.mp4

Date
07/03/2018
W/O
712060
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00249
PipeID
P03454
Time
3:41 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4004
Sewer Name
02 DOWNEY TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Maintenance Related
Project
WO_712060_TV02050_JUL2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0885
Downstream MH
02 0886
Dir. of Survey
Upstream
Length Surveyed
227.4 ft.
Total Length
227.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 02 0885 to 02 0886
MH: 02 0885MH: 02 0886upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 08861.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish69.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"73.2 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 8", 2"79.1 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"127.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"225.3 ft. MGO - General Observation - MAG COAT225.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start225.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start227.4 ft. MWM - Water Mark, 50 %of cross sectional area227.4 ft. MWL - Water Level, 15 %of cross sectional area227.4 ft. AMH - Downstream Manhole, Survey Begins - 02 0885

Observation photos (3)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 8", 2"

    154.2 ft. - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 8", 2"

Observations (13)

DistanceCodeObservation
157.5TFC
100.2TB
225.9SAV
0MWM
2.1MGOMAG COAT
2.1SAV
0MWL
2.1DAGS
227.4AMH02 0886
0AMH02 0885
154.2TBI
148.3TB
225.9DAGS

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2018-07-03T03:41:29-07:00