Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 26, 2018, 07:33 AM
  • 18 0848_18 0847 _26062018_011120.mp4

Date
06/26/2018
W/O
707024
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00709
PipeID
P14703
Time
12:33 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5200
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37A
Purpose
Routine Assessment
Project
WO_707024_TV18101_JUN2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Width
51 in.
Upstream MH
18 0848
Downstream MH
18 0847
Dir. of Survey
Downstream
Length Surveyed
706.4 ft.
Total Length
706.4 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
3
O&M Quick
4221
O&M Rating
10
Overall Index
4
Overall Quick
Overall Rating
18
Pipe schematic from manhole 18 0848 to 18 0847
MH: 18 0848MH: 18 0847downstream0 ft. MWL - Water Level, 45 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08480 ft. LL - Alignment Left, 25 %, Start18.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start31.6 ft. LL - Alignment Left, 25 %, Finish31.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start66.6 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start - MAGNEZIUM H.O COATING start706.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish706.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish706.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0847706.4 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18.3 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    31.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Other, 5 %of cross sectional area, from 10 to 02 o'clock,  , within 8 inches of joint: YES, Start - MAGNEZIUM H.O COATING start

    66.6 ft. - Deposits Attached Other, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start - MAGNEZIUM H.O COATING start

Observations (12)

DistanceCodeObservation
0MWL
706.4SAP
31.7SAP
0MWM
0AMH18 0848
706.4SRV
31.6LL
18.3SRV
706.4AMH18 0847
66.6DAZMAGNEZIUM H.O COATING start
706.4DAZ
0LL

Properties (4)

additional_info
SC359525
custom_field_two
2
customer
LACSD
datetime
2018-06-26T00:33:50-07:00