- Date
- 06/07/2018
- W/O
- 707024
- Weather
- Dry
- Operator/Surveyor
- K. ADAME
- Sewer ID
- Z00709
- PipeID
- P14739
- Time
- 11:53 PM
- Certificate
- U-0817-07009000
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K5644
- Sewer Name
- 18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
- City
- WHITTIER, CA
- Loc. details
- Main Highway - Suburban/Rural
- Location Code
- B
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 26
- Purpose
- Routine Assessment
- Project
- WO_707024_TV18101_JUN2018
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Width
- 24 in.
- Upstream MH
- 18 0888
- Downstream MH
- 18 0887
- Dir. of Survey
- Downstream
- Length Surveyed
- 765.8 ft.
- Total Length
- 765.8 ft.
- Structural Index
- 4
- Structural Quick
- 5432
- Structural Rating
- 26
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 26
Pipe schematic from manhole 18 0888 to 18 0887 Observation photos (6)

7.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

23.6 ft. - Surface Reinforcement Corroded, from 08 to 09 o'clock, within 8 inches of joint: NO, Start

23.7 ft. - Surface Reinforcement Corroded, from 03 to 04 o'clock, within 8 inches of joint: NO, Start

483.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

499.1 ft. - Surface Reinforcement Corroded, from 07 to 08 o'clock, within 8 inches of joint: NO, Start

499.1 ft. - Surface Reinforcement Corroded, from 04 to 05 o'clock, within 8 inches of joint: NO, Start