Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2018, 07:53 AM
  • 18 0887_18 0886 _03072018_164912.mp4

Date
06/08/2018
W/O
707024
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00709
PipeID
P14738
Time
12:53 AM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5644
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
WHITTIER, CA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
WO_707024_TV18101_JUN2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0887
Downstream MH
18 0886
Dir. of Survey
Downstream
Length Surveyed
599.4 ft.
Total Length
599.4 ft.
Structural Index
4
Structural Quick
5231
Structural Rating
13
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
13
Pipe schematic from manhole 18 0887 to 18 0886
MH: 18 0887MH: 18 0886downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 08870 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area6.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start6.9 ft. MGO - General Observation - MAGNESIUM COATING START62.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish62.6 ft. SRC - Surface Reinforcement Corroded, from 07 to 08 o'clock, within 8 inches of joint: NO, Start62.6 ft. SRC - Surface Reinforcement Corroded, from 04 to 05 o'clock, within 8 inches of joint: NO, Start104.7 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"594.7 ft. SRC - Surface Reinforcement Corroded, from 07 to 08 o'clock, within 8 inches of joint: NO, Finish594.7 ft. SRC - Surface Reinforcement Corroded, from 04 to 05 o'clock, within 8 inches of joint: NO, Finish599.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0886599.4 ft. MGO - General Observation - MAGNESIUM COATING END

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    6.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Corroded, from 07 to 08 o'clock, within 8 inches of joint: NO, Start

    62.6 ft. - Surface Reinforcement Corroded, from 07 to 08 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Corroded, from 04 to 05 o'clock, within 8 inches of joint: NO, Start

    62.6 ft. - Surface Reinforcement Corroded, from 04 to 05 o'clock, within 8 inches of joint: NO, Start

Observations (13)

DistanceCodeObservation
599.4AMH18 0886
62.6SRC
0AMH18 0887
104.7TB
62.6SRC
594.7SRC
0MWM
62.4SAP
599.4MGOMAGNESIUM COATING END
0MWL
6.9MGOMAGNESIUM COATING START
6.1SAP
594.7SRC

Properties (4)

additional_info
SC359199
custom_field_two
2
customer
LACSD
datetime
2018-06-08T00:53:27-07:00