Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2018, 09:04 AM
  • A 0812_A 0345 _11062018_021730.mp4

Date
06/11/2018
W/O
706931
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00325
PipeID
P08312
Time
2:04 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5694
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
16
Purpose
Routine Assessment
Project
WO_706931_TV15003_JUN2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
A 0812
Downstream MH
A 0345
Dir. of Survey
Downstream
Length Surveyed
406.5 ft.
Total Length
406.5 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
400
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
400
Pipe schematic from manhole A 0812 to A 0345
MH: A 0812MH: A 0345downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 08120 ft. MWL - Water Level, 20 %of cross sectional area6.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start406.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish406.5 ft. MSA - Survey Abandoned - BOAT FLIPPED OVER DUE TO BEND IN PIPE406.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Survey Abandoned - BOAT FLIPPED OVER DUE TO BEND IN PIPE

    406.5 ft. - Survey Abandoned - BOAT FLIPPED OVER DUE TO BEND IN PIPE

Observations (8)

DistanceCodeObservation
406.5SAV
406.5MSABOAT FLIPPED OVER DUE TO BEND IN PIPE
0MWM
0AMHA 0812
6.2SSS
406.5SSS
0MWL
6.2SAV

Properties (5)

additional_info
SC359652
custom_field_two
3
customer
LACSD
datetime
2018-06-11T02:04:07-07:00
year_laid
29427