02 0006_02 0005A_05062018_010043.mp4
3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start
7.2 ft. - Crack Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES, Start
19.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start
24.8 ft. - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start
47.1 ft. - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES
52.7 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start
| Distance | Code | Observation |
|---|---|---|
| 0 | AMH | 02 0006 |
| 47.1 | FS | — |
| 285.2 | AMH | 02 0005A |
| 18.9 | CS | — |
| 192.4 | TB | — |
| 40.5 | FS | — |
| 244.7 | TBC | — |
| 52.7 | CM | — |
| 7.2 | CS | — |
| 283 | FM | — |
| 19.3 | CM | — |
| 195.9 | TBA | — |
| 0 | MWL | — |
| 0 | MWM | — |
| 283 | DAGS | — |
| 24.8 | FS | — |
| 45.8 | TBA | — |
| 52.7 | FM | — |
| 115.2 | TBA | — |
| 3 | DAGS | — |