Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2018, 08:58 AM
  • 15 0096_15 0075_20062018_021946.mp4

Date
06/20/2018
W/O
706913
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00590
PipeID
P11973
Time
1:58 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5737
Sewer Name
15 ABBEY STREET TRUNK
City
INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
WO_706913_TV15007_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0096
Downstream MH
15 0075
Dir. of Survey
Downstream
Length Surveyed
241.3 ft.
Total Length
241.3 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2I00
O&M Rating
96
Overall Index
2
Overall Quick
Overall Rating
101
Pipe schematic from manhole 15 0096 to 15 0075
MH: 15 0096MH: 15 0075downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 15 00960 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4", 4"9.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"70.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"73.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"118.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"121.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"170.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"173.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"218.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"221.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"232.1 ft. CS - Crack Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES238.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES241.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE241.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK241.3 ft. AMH - Downstream Manhole, Survey Ends - 15 0075241.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES

    232.1 ft. - Crack Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    238.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
70.6TFC
9.6TFC
173.3TFC
0MWM
241.3MGOCOCKROACHES IN MANHOLE
73.4TFC
241.3MGOACTIVE CONNECTION AT MH 9 O'CLOCK
241.3AMH15 0075
238.7CM
241.3DAGS
7.2TFC
0MGOCOCKROACHES IN MANHOLE
121.7TFC
2DAGS
218.3TFC
221.3TFC
232.1CS
118.8TFC
0AMH15 0096
170.4TF
0MWL

Properties (4)

additional_info
SC359703
custom_field_two
4
customer
LACSD
datetime
2018-06-20T01:58:59-07:00