Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 19, 2018, 08:46 AM
  • 15 0107_15 0106 _19062018_015753.mp4

Date
06/19/2018
W/O
706913
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00590
PipeID
P11985
Time
1:46 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5734
Sewer Name
15 ABBEY STREET TRUNK
City
LA PUENTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
WO_706913_TV15007_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0107
Downstream MH
15 0106
Dir. of Survey
Downstream
Length Surveyed
171.1 ft.
Total Length
171.1 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
81
O&M Index
2
O&M Quick
2F00
O&M Rating
66
Overall Index
2
Overall Quick
Overall Rating
147
Pipe schematic from manhole 15 0107 to 15 0106
MH: 15 0107MH: 15 0106downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 01072 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start32 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start66.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"69.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"81.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"95.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"101.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"134.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"149.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"169.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish169.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish171.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0106

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    32 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
2DAGS
32CM
0MWL
69.3TFC
0MWM
95.8TFA
81.2TFA
0AMH15 0107
66.6TFC
134.5TFC
171.1AMH15 0106
169.2CM
101.4TFA
149.1TFA
169.2DAGS

Properties (4)

additional_info
SC359400
custom_field_two
3
customer
LACSD
datetime
2018-06-19T01:46:15-07:00