Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 12, 2018, 06:09 AM
  • 20 0436_20 0435 _11062018_232145.mp4

Date
06/11/2018
W/O
706912
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00749
PipeID
P19384
Time
11:09 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5725
Sewer Name
20 10TH STREET EAST CONNECTION TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
12
Purpose
Routine Assessment
Project
WO_706912_TV20001_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
20 0436
Downstream MH
20 0435
Dir. of Survey
Downstream
Length Surveyed
266.4 ft.
Total Length
266.4 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
2
O&M Quick
2J00
O&M Rating
106
Overall Index
3
Overall Quick
Overall Rating
262
Pipe schematic from manhole 20 0436 to 20 0435
MH: 20 0436MH: 20 0435downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 20 04360 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start8.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"23.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"86.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"87.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"89 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"140.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"143.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"194.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"196.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"266.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK266.4 ft. AMH - Downstream Manhole, Survey Ends - 20 0435266.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish266.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE266.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
266.4MGOACTIVE CONNECTION AT MH 9 O'CLOCK
89TFC
266.4AMH20 0435
8.1CM
0MWL
266.4DAGS
266.4MGOCOCKROACHES IN MANHOLE
86.2TF
0MGOCOCKROACHES IN MANHOLE
87.1TBA
23.5TFC
20.4TFC
140.5TFC
194.9TFC
266.4CM
0AMH20 0436
143.1TFC
196.8TFC
2DAGS
0MWM

Properties (4)

additional_info
SC359391
custom_field_two
3
customer
LACSD
datetime
2018-06-11T23:09:34-07:00