Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2018, 11:20 AM
  • 02 1387_02 1386 _04062018_044555.mp4

Date
06/04/2018
W/O
706877
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00242
PipeID
P03905
Time
4:20 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5184
Sewer Name
02 CLOVERLAWN TRUNK
City
SOUTH GATE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
31
Purpose
Routine Assessment
Project
WO_706877_TV02041_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
02 1387
Downstream MH
02 1386
Dir. of Survey
Downstream
Length Surveyed
342.9 ft.
Total Length
342.9 ft.
Structural Index
3
Structural Quick
4237
Structural Rating
33
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
35
Pipe schematic from manhole 02 1387 to 02 1386
MH: 02 1387MH: 02 1386downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 13870 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area12.9 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES14.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start23.3 ft. CS - Crack Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES30.2 ft. FS - Fracture Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES32.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"40.6 ft. CM - Crack Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES41.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"70.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES91.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start142.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"196 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"235.3 ft. FM - Fracture Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES255.7 ft. FS - Fracture Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES330.8 ft. FS - Fracture Spiral, from 06 to 10 o'clock, within 8 inches of joint: YES334.4 ft. FS - Fracture Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES337.7 ft. FM - Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES340.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish340.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish342.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1386

Observation photos (12)

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    12.9 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    14.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES

    23.3 ft. - Crack Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES

    30.2 ft. - Fracture Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES

    40.6 ft. - Crack Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    70.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    93.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES

    235.3 ft. - Fracture Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES

    255.7 ft. - Fracture Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 06 to 10 o'clock, within 8 inches of joint: YES

    330.8 ft. - Fracture Spiral, from 06 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES

    334.4 ft. - Fracture Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

    337.7 ft. - Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
0AMH02 1387
330.8FS
340.8DAGS
70.3CM
41.5TFC
14.7DAGS
91.7TFC
0MWL
30.2FS
255.7FS
196TFC
340.8CM
93.4CM
12.9CL
235.3FM
142.5TFC
40.6CM
342.9AMH02 1386
32.7TB
0MWM
337.7FM
334.4FS
23.3CS