Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 6, 2018, 06:00 AM
  • 18 0040_18 0039 _05062018_234051.mp4

Date
06/05/2018
W/O
707282
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00689
PipeID
P13855
Time
11:00 PM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5638
Sewer Name
18 MILLS AVENUE TRUNK
City
WHITTTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_707282_TV18176_JUN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0040
Downstream MH
18 0039
Dir. of Survey
Downstream
Length Surveyed
230.9 ft.
Total Length
230.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0040 to 18 0039
MH: 18 0040MH: 18 0039downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00400 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK0 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK2.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start20.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"72.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"82.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"140.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"145.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"161.3 ft. MGO - General Observation - MAGNESIUM COATING START192.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"198.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"230.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish230.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0039

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

Observations (16)

DistanceCodeObservation
230.9SAP
0AMH18 0040
230.9AMH18 0039
145.9TFC
161.3MGOMAGNESIUM COATING START
0MWM
72.8TFC
82.5TFC
2.2SAP
192.5TFC
20.1TFC
140.3TFC
0MWL
0MGOCONNECTION AT MH 3 OCLOCK
198.2TFC
0MGOCONNECTION AT MH 9 OCLOCK

Properties (4)

additional_info
SC359193
custom_field_two
2
customer
LACSD
datetime
2018-06-05T23:00:25-07:00