Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 6, 2018, 05:15 AM
  • 18 0041_18 0040 _05062018_222832.mp4

Date
06/05/2018
W/O
707282
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00689
PipeID
P13856
Time
10:15 PM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5638
Sewer Name
18 MILLS AVENUE TRUNK
City
WHITTTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_707282_TV18176_JUN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0041
Downstream MH
18 0040
Dir. of Survey
Downstream
Length Surveyed
245 ft.
Total Length
245 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0041 to 18 0040
MH: 18 0041MH: 18 0040downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00410 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.1 ft. MGO - General Observation - MAGNESIUM COATING START2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start23.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"29.2 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"62.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"68.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"141.5 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"150.9 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"208.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"244.7 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK244.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0040244.7 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK245 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

Observations (16)

DistanceCodeObservation
244.7MGOCONNECTION AT MH 9 OCLOCK
0AMH18 0041
244.7AMH18 0040
150.9TFC
2.1MGOMAGNESIUM COATING START
141.5TFC
62.3TFC
68.7TFC
29.2TFC
0MWM
245SAP
0MWL
208.5TFC
244.7MGOCONNECTION AT MH 3 OCLOCK
2.1SAP
23.3TFC

Properties (4)

additional_info
SC359193
custom_field_two
2
customer
LACSD
datetime
2018-06-05T22:15:04-07:00