Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2018, 07:36 AM
  • 18 0060_18 0059 _01062018_010059.mp4

Date
06/01/2018
W/O
707282
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00689
PipeID
P13874
Time
12:36 AM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5632
Sewer Name
18 MILLS AVENUE TRUNK
City
WHITTTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_707282_TV18176_JUN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0060
Downstream MH
18 0059
Dir. of Survey
Downstream
Length Surveyed
401.9 ft.
Total Length
401.9 ft.
Structural Index
3
Structural Quick
4334
Structural Rating
28
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
28
Pipe schematic from manhole 18 0060 to 18 0059
MH: 18 0060MH: 18 0059downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00600 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"36.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES38.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"59.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"64.7 ft. MGO - General Observation - MAGNESIUM COATING START85.5 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES109.7 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES123.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"145 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"154.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"164.6 ft. FM - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES166.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"197.8 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES205.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"210.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES231.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES254.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"264 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"291.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"335.1 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES346 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"379.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"401.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish401.8 ft. MGO - General Observation - MAGNESIUM COATING END401.9 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK401.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0059

Observation photos (9)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    36.9 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    85.5 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    109.7 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    164.6 ft. - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    197.8 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    210.2 ft. - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    231.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    335.1 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (30)

DistanceCodeObservation
205.9TF
109.7CL
401.9MGOCONNECTION AT MH 3 OCLOCK
154.3TF
210.2FL
291.2TF
401.8SAV
59.8TF
166.4TF
401.9AMH18 0059
401.8MGOMAGNESIUM COATING END
38.5TF
145TF
335.1FM
346TF
379.4TF
164.6FM
123.5TF
0AMH18 0060
231.4FM
36.9FL
254.7TF
35.6TF
197.8FL
85.5CL
64.7MGOMAGNESIUM COATING START
0MWM
0MWL
2SAV
264TF