Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2018, 08:37 AM
  • A 0814_A 0813 _11062018_015249.mp4

Date
06/11/2018
W/O
707026
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00325
PipeID
P08314
Time
1:37 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5693
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
16
Purpose
Routine Assessment
Project
WO_707026_TV15209_JUN2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
A 0814
Downstream MH
A 0813
Dir. of Survey
Downstream
Length Surveyed
145.8 ft.
Total Length
145.8 ft.
Structural Index
3
Structural Quick
573E
Structural Rating
119
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
119
Pipe schematic from manhole A 0814 to A 0813
MH: A 0814MH: A 0813downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 08140 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start37.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish141.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish145.8 ft. AMH - Downstream Manhole, Survey Ends - A 0813

Observation photos (2)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0AMHA 0814
37.1SRV
2.1SRV
141.2SAP
2.1SAP
145.8AMHA 0813
0MWM
0MWL

Properties (5)

additional_info
SC359651
custom_field_two
2
customer
LACSD
datetime
2018-06-11T01:37:33-07:00
year_laid
29427