Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2018, 07:08 AM
  • 05 1268_05 1267 _15062018_001618.mp4

Date
06/15/2018
W/O
706881
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00518
PipeID
P06480
Time
12:08 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5731
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
WO_706881_TV05332_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1268
Downstream MH
05 1267
Dir. of Survey
Downstream
Length Surveyed
133 ft.
Total Length
133 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
66
O&M Index
2
O&M Quick
2D00
O&M Rating
54
Overall Index
2
Overall Quick
Overall Rating
120
Pipe schematic from manhole 05 1268 to 05 1267
MH: 05 1268MH: 05 1267downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 12680 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start22.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start56.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"64.2 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 4", 1"121.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"133 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish133 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish133 ft. AMH - Downstream Manhole, Survey Ends - 05 1267133 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    22.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 4", 1"

    64.2 ft. - Tap Break-In Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 4", 1"

Observations (13)

DistanceCodeObservation
133DAGS
0AMH05 1268
121.1TFC
0MWL
64.2TBI
0MWM
133CM
2DAGS
56.5TFC
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
133AMH05 1267
133MGOACTIVE CONNECTION AT MH 9 O'CLOCK
22.9CM

Properties (4)

additional_info
SC359397
custom_field_two
3
customer
LACSD
datetime
2018-06-15T00:08:48-07:00