Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2018, 06:15 AM
  • 05 1270_05 1269 _14062018_233340.mp4

Date
06/14/2018
W/O
706881
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00518
PipeID
P06482
Time
11:15 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5731
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
WO_706881_TV05332_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1270
Downstream MH
05 1269
Dir. of Survey
Downstream
Length Surveyed
341.6 ft.
Total Length
341.6 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
192
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
332
Pipe schematic from manhole 05 1270 to 05 1269
MH: 05 1270MH: 05 1269downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 12700 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start17.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start63.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"79.4 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 4", 2"152.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"172.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"225.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"228.8 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 4", 2"261.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"289.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"340.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish340.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish341.6 ft. AMH - Downstream Manhole, Survey Ends - 05 1269341.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    17.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 4", 2"

    79.4 ft. - Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 4", 2"

  • Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 4", 2"

    228.8 ft. - Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 4", 2"

Observations (18)

DistanceCodeObservation
0AMH05 1270
0MWL
341.6AMH05 1269
0MWM
228.8TBI
2DAGS
289.3TFC
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
340.3CM
172.8TB
340.3DAGS
225.4TF
152.6TFC
79.4TBI
341.6MGOACTIVE CONNECTION AT MH 9 O'CLOCK
17.8CM
63.6TF
261.1TFC

Properties (4)

additional_info
SC359397
custom_field_two
3
customer
LACSD
datetime
2018-06-14T23:15:40-07:00