Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2018, 02:53 PM
  • H 0665_H 0664 _08062018_081243.mp4

Date
06/08/2018
W/O
701651
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00941
PipeID
P11072
Time
7:53 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4001
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
PICO RIVERA, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
03
Purpose
Maintenance Related
Project
WO_701651_TV18175_MAY2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
28 in.
Width
28 in.
Upstream MH
H 0665
Downstream MH
H 0664
Dir. of Survey
Downstream
Length Surveyed
502.6 ft.
Total Length
502.6 ft.
Structural Index
3
Structural Quick
3S00
Structural Rating
300
O&M Index
2
O&M Quick
412d
O&M Rating
372
Overall Index
2
Overall Quick
Overall Rating
672
Pipe schematic from manhole H 0665 to H 0664
MH: H 0665MH: H 0664downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 06650 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start81.8 ft. OBZ - Obstacles Other, 5 %of cross sectional area, at 06 o'clock, Start - UNKNOWN UNDER FLOW501.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish501.2 ft. OBZ - Obstacles Other, 5 %of cross sectional area, at 06 o'clock, Finish - UNKNOWN UNDER FLOW501.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish502.6 ft. AMH - Downstream Manhole, Survey Ends - H 0664

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0AMHH 0665
0MWL
501.2DAGS
0MWM
2.1MGOMAG COAT
502.6AMHH 0664
501.2OBZUNKNOWN UNDER FLOW
501.2SAV
81.8OBZUNKNOWN UNDER FLOW
2.1DAGS
2.1SAV

Properties (3)

custom_field_two
2
customer
LACSD
datetime
2018-06-08T07:53:08-07:00