Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 26, 2018, 06:06 AM
  • 02 0008_02 0007 _31052018_233631.mp4

Date
05/25/2018
W/O
706730
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00234
PipeID
P03034
Time
11:06 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5181
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
WO_706730_TV02341_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 0008
Downstream MH
02 0007
Dir. of Survey
Downstream
Length Surveyed
375.5 ft.
Total Length
375.5 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
12
O&M Index
2
O&M Quick
3124
O&M Rating
13
Overall Index
2
Overall Quick
Overall Rating
25
Pipe schematic from manhole 02 0008 to 02 0007
MH: 02 0008MH: 02 0007downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 00080 ft. MWM - Water Mark, 35 %of cross sectional area2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES16 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start16.6 ft. RMC - Roots Medium Connection, from 11 to 04 o'clock, 50 %, within 8 inches of joint: YES20.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"92.3 ft. RFJ - Roots Fine Joint, from 09 to 01 o'clock, within 8 inches of joint: YESR93.2 ft. RFC - Roots Fine Connection, at 12 o'clock, within 8 inches of joint: NO94.1 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"147.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES148.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"195.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish209.8 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES212 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"235.2 ft. CS - Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES265.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO266.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"331.2 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"351 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"370.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES372.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish375.5 ft. AMH - Downstream Manhole, Survey Ends - 02 0007

Observation photos (11)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    7.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    16 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 11 to 04 o'clock, 50 %, within 8 inches of joint: YES

    16.6 ft. - Roots Medium Connection, from 11 to 04 o'clock, 50 %, within 8 inches of joint: YES

  • Roots Fine Joint, from 09 to 01 o'clock, within 8 inches of joint: YESR

    92.3 ft. - Roots Fine Joint, from 09 to 01 o'clock, within 8 inches of joint: YESR

  • Roots Fine Connection, at 12 o'clock, within 8 inches of joint: NO

    93.2 ft. - Roots Fine Connection, at 12 o'clock, within 8 inches of joint: NO

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES

    147.1 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES

    209.8 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES

  • Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES

    235.2 ft. - Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: NO

    265.2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    370.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
0MWL
16FM
372.8DAGS
94.1TBA
147.1DAGS
7.9CM
209.8DAGS
235.2CS
351TB
370.4CM
92.3RFJ
212TB
195.2FM
2.2DAGS
0AMH02 0008
0MWM
16.6RMC
20.7TB
331.2TB
148.7TB
266.9TB
93.2RFC
375.5AMH02 0007
265.2DAGS

Properties (4)

additional_info
SC359502
custom_field_two
2
customer
LACSD
datetime
2018-05-25T23:06:38-07:00