Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 6, 2018, 10:25 AM
  • B 0454A_B 0454 _06062018_033147.mp4

Date
06/06/2018
W/O
706794
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00093
PipeID
P08967
Time
3:25 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5689
Sewer Name
B JOINT OUTFALL B - UNIT 5C
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
WO_706794_TV16033_JUN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
B 0454A
Downstream MH
B 0454
Dir. of Survey
Downstream
Length Surveyed
121.5 ft.
Total Length
121.5 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
72
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
72
Pipe schematic from manhole B 0454A to B 0454
MH: B 0454AMH: B 0454downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 0454A0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.8 ft. MGO - General Observation - MAG COAT7.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"22.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"74.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"121.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK121.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish121.5 ft. AMH - Downstream Manhole, Survey Ends - B 0454

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
22.8TFC
121.5MGOCONNECTION AT MH 9 O'CLOCK
74.2TFC
7.8TFC
121.5SAV
121.5AMHB 0454
2.8SAV
0AMHB 0454A
93.2TFC
0MWL
0MWM
2.8MGOMAG COAT

Properties (4)

additional_info
SC359348
custom_field_two
3
customer
LACSD
datetime
2018-06-06T03:25:06-07:00