Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2018, 09:04 AM
  • F 0032_F 0031_6212018_032810.mp4

Date
06/21/2018
W/O
0711445
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10207
Time
2:04 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0897
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
PARAMOUNT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20180620MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0032
Downstream MH
F 0031
Dir. of Survey
Downstream
Length Surveyed
285.7 ft.
Total Length
285.7 ft.
Structural Index
5
Structural Quick
5641
Structural Rating
34
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
34
Pipe schematic from manhole F 0032 to F 0031
MH: F 0032MH: F 0031downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN STOPLOG IN PLACE0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:35AM2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR2 ft. MGO - General Observation - MAG COAT 70% START 8:00 TO 4:0015 ft. SRC - Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR40 ft. SRC - Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: YES - CORODED MISSING REBAR79.3 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR89.9 ft. MGO - General Observation - MAG COAT 70% FINISH129.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR183.5 ft. SRC - Surface Reinforcement Corroded, from 08 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR261 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active285.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG285.3 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR285.7 ft. AMH - Downstream Manhole, Survey Ends - 3:55AM

Observation photos (10)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

  • General Observation - MAG COAT 70% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 70% START 8:00 TO 4:00

  • Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    15 ft. - Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: YES - CORODED MISSING REBAR

    40 ft. - Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: YES - CORODED MISSING REBAR

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

    79.3 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

  • General Observation - MAG COAT 70% FINISH

    89.9 ft. - General Observation - MAG COAT 70% FINISH

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    129.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 08 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    183.5 ft. - Surface Reinforcement Corroded, from 08 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR

    285.3 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR

Observations (17)

DistanceCodeObservation
79.3SRCLONG REBAR
40SRCCORODED MISSING REBAR
285.3SAMSEVERE AGG
129.7SRCCIRCUM REBAR
261TFActive
183.5SRCCIRCUM REBAR
2SAMSEVERE AGG
285.7AMH3:55AM
0MWL
2SRCLONG & CIRCUM REBAR
0MGOConn. @ Mh, 9 O' Clock. OPEN STOPLOG IN PLACE
285.3SRCLONG & CIRCUM REBAR
0MWM
0AMH3:35AM
89.9MGOMAG COAT 70% FINISH
15SRCCIRCUM REBAR
2MGOMAG COAT 70% START 8:00 TO 4:00

Properties (4)

custom_field_three
LONG & CIRCUM REBAR CORRODED & MISSING
custom_field_two
2
customer
LACSD
datetime
2018-06-21T02:04:02-07:00