Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2018, 07:54 PM
  • 02 2342_02 2341_6202018_133656.mp4

Date
06/20/2018
W/O
0712243
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00896
PipeID
P20972
Time
12:54 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7735
Sewer Name
02 ARTHUR AVENUE TRUNK
City
PARAMOUNT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
31
Purpose
Routine Assessment
Project
20180620DF_ARTHUR_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 2342
Downstream MH
02 2341
Dir. of Survey
Downstream
Length Surveyed
265.6 ft.
Total Length
265.6 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 2342 to 02 2341
MH: 02 2342MH: 02 2341downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:57 PM0.1 ft. MWM - Water Mark, 25 %of cross sectional area0.1 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open55.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open89.1 ft. MGP - General Photograph93.6 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 4"132.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open170.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 4"207.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open245.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open263 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish265.6 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)265.6 ft. AMH - Downstream Manhole, Survey Ends - 1:53 PM

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    89.1 ft. - General Photograph

Observations (15)

DistanceCodeObservation
19.5TFOpen
0.1MWM
0.1MWL
265.6MGOGREASE THROUGHOUT THE REACH (5%)
265.6AMH1:53 PM
263SSS
170.5TFA
0AMH12:57 PM
55.1TFOpen
207.5TFOpen
89.1MGP
2SSS
93.6TFA
245.9TFOpen
132.6TFOpen

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2018-06-20T12:54:10-07:00