Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 19, 2018, 10:38 AM
  • Section#2_F 0030_F 0029__6192018__I0029.mp4

Date
06/19/2018
W/O
0711445
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10120
Time
3:38 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0029
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
PARAMOUNT
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20180619MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0030
Downstream MH
F 0029
Dir. of Survey
Downstream
Length Surveyed
525.1 ft.
Total Length
525.1 ft.
Structural Index
5
Structural Quick
5V4T
Structural Rating
995
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
995
Pipe schematic from manhole F 0030 to F 0029
MH: F 0030MH: F 0029downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:45AM0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG33 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR111.4 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR144.8 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish - CIRCUM REBAR188.8 ft. MGO - General Observation - 80% MAG COAT START205.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR483.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR525.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR525.1 ft. MGO - General Observation - 80% MAG COAT FINISH525.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG

Observation photos (7)

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start -  CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    33 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

    111.4 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

  • General Observation - 80% MAG COAT START

    188.8 ft. - General Observation - 80% MAG COAT START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    205.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    483.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

Observations (14)

DistanceCodeObservation
483.6SRCCIRCUM REBAR
0MWM
2SRCCIRCUM REBAR
33SRCCIRCUM REBAR
525.1SRCCIRCUM REBAR
111.4SRCCIRCUM REBAR
525.1MGO80% MAG COAT FINISH
144.8SRCCIRCUM REBAR
205.6SRCCIRCUM REBAR
188.8MGO80% MAG COAT START
525.1SAMSEVERE AGG
2SAMSEVERE AGG
0AMH3:45AM
0MWL

Properties (4)

custom_field_three
CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2018-06-19T03:38:34-07:00