Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 29, 2018, 08:54 AM
  • 01 0266_01 0265_29052018_022222.mp4

Date
05/29/2018
W/O
707007
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00218
PipeID
P01312
Time
1:54 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5176
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_707007_TV01204_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 0266
Downstream MH
01 0265
Dir. of Survey
Downstream
Length Surveyed
334.3 ft.
Total Length
334.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 01 0266 to 01 0265
MH: 01 0266MH: 01 0265downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02660 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH1.8 ft. MGO - General Observation - LINER1.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start111.7 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"138.7 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6" - SPIRAL CRACK INSIDE207.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"267.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"332.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish334.3 ft. MGO - General Observation - CAPPED CONNECTION AT 9 O' CLOCK AT334.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0265334.3 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    1.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
138.7TFDSPIRAL CRACK INSIDE
111.7TF
267.8TF
332.5DAGS
1.8MGOLINER
1.8DAGS
0MWM
0MWL
0AMH01 0266
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
207.4TF
334.3MGOCAPPED CONNECTION AT 9 O' CLOCK AT
334.3AMH01 0265
334.3MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH

Properties (5)

additional_info
SC355097
custom_field_two
4
customer
LACSD
datetime
2018-05-29T01:54:52-07:00
lining
CIPP