Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 29, 2018, 10:47 AM
  • 01 0260_01 0259_29052018_040043.mp4

Date
05/29/2018
W/O
707007
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00218
PipeID
P01306
Time
3:47 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5176
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_707007_TV01204_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0260
Downstream MH
01 0259
Dir. of Survey
Downstream
Length Surveyed
323.4 ft.
Total Length
323.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
412L
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
138
Pipe schematic from manhole 01 0260 to 01 0259
MH: 01 0260MH: 01 0259downstream0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Begins - 01 02600 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start7.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start99.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"141.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"180 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN, OPERATOR DID NOT STOP TO LOOK AT CONN.217 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"259.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"320.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish320.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish323.4 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH323.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0259

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
2.4DAGS
217TF
320.9CM
0AMH01 0260
0MWM
259.1TFA
141.7TF
7.1CM
99.6TF
320.9DAGS
180TFUNKNOWN, OPERATOR DID NOT STOP TO LOOK AT CONN.
323.4MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
323.4AMH01 0259
0MWL

Properties (4)

additional_info
SC355097
custom_field_two
3
customer
LACSD
datetime
2018-05-29T03:47:55-07:00