Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 29, 2018, 11:01 AM
  • 01 0259_01 0258_29052018_041522.mp4

Date
05/29/2018
W/O
707007
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00218
PipeID
P01305
Time
4:01 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5176
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_707007_TV01204_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0259
Downstream MH
01 0258
Dir. of Survey
Downstream
Length Surveyed
313.2 ft.
Total Length
313.2 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
4122
O&M Rating
13
Overall Index
2
Overall Quick
Overall Rating
19
Pipe schematic from manhole 01 0259 to 01 0258
MH: 01 0259MH: 01 0258downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Begins - 01 02592.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start114.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"157 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"196.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"243 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN, OPERATOR DID NOT STOP TO LOOK AT CONN.265.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start291.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish310.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish310.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish313.2 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH313.2 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH313.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0258

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    265.7 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

Observations (17)

DistanceCodeObservation
0MWL
114.6TFA
265.7RFJ
243TFUNKNOWN, OPERATOR DID NOT STOP TO LOOK AT CONN.
310.6DAGS
0MWM
196.1TF
310.6CM
3.7CM
291.6RFJ
313.2MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
313.2MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
313.2AMH01 0258
2.2DAGS
157TFA
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
0AMH01 0259

Properties (4)

additional_info
SC355097
custom_field_two
3
customer
LACSD
datetime
2018-05-29T04:01:40-07:00