Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2018, 05:25 AM
  • 15 0186_15 0185 _31052018_230040.mp4

Date
05/31/2018
W/O
701427
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00605
PipeID
P12110
Time
10:25 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5680
Sewer Name
15 FERRIS ROAD TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_701427_TV15127_MAY2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0186
Downstream MH
15 0185
Dir. of Survey
Downstream
Length Surveyed
74.9 ft.
Total Length
74.9 ft.
Structural Index
3
Structural Quick
3A22
Structural Rating
40
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
40
Pipe schematic from manhole 15 0186 to 15 0185
MH: 15 0186MH: 15 0185downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 01863.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES5.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES12.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"53.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"72.5 ft. MGO - General Observation - LINK PIPE74.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish74.9 ft. MSA - Survey Abandoned - CAM BLKD BY LINK PIPE

Observation photos (4)

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    3.1 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    5.1 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - LINK PIPE

    72.5 ft. - General Observation - LINK PIPE

Observations (11)

DistanceCodeObservation
0MWL
0MWM
12.2CM
72.5MGOLINK PIPE
3.1CL
74.7CM
0AMH15 0186
74.9MSACAM BLKD BY LINK PIPE
53.3TF
34.1TF
5.1CL

Properties (4)

additional_info
SC359338
custom_field_two
3
customer
LACSD
datetime
2018-05-31T22:25:49-07:00