Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2018, 06:41 AM
  • 15 0186_15 0185 _01062018_000353.mp4

Date
05/31/2018
W/O
701427
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00605
PipeID
P12110
Time
11:41 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5680
Sewer Name
15 FERRIS ROAD TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_701427_TV15127_MAY2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0185
Downstream MH
15 0186
Dir. of Survey
Upstream
Length Surveyed
276.6 ft.
Total Length
276.6 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 15 0185 to 15 0186
MH: 15 0185MH: 15 0186upstream0 ft. MSA - Survey Abandoned - REVERSAL COMPLETED0 ft. MGO - General Observation - LINK PIPE0 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"10.2 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES36.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"42.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"152.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"171.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"173 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES198.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"213.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"223.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"274.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"276.6 ft. MWM - Water Mark, 20 %of cross sectional area276.6 ft. MGO - Reversal Inspection276.6 ft. AMH - Downstream Manhole, Survey Begins - 15 0185276.6 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (3)

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    103.6 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    266.4 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • General Observation - LINK PIPE

    276.6 ft. - General Observation - LINK PIPE

Observations (21)

DistanceCodeObservation
0MWM
78.2TFC
176.4TF
103.6CM
276.6MSAREVERSAL COMPLETED
105.3TF
53.4TFC
266.4CL
276.6MGOLINK PIPE
123.8TF
2.1TF
0MGO
240.3TFC
151.5TFC
0AMH15 0185
276.6TF
170.1TFC
233.7TFC
0MWL
63.5TFC
203.9TF

Properties (4)

additional_info
SC359338
custom_field_two
3
customer
LACSD
datetime