Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2018, 07:14 AM
  • 18 0744_18 0743 _10052018_002055.mp4

Date
05/10/2018
W/O
701125
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00706
PipeID
P14597
Time
12:14 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5317
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_701125_TV18104_MAY2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
18 0744
Downstream MH
18 0743
Dir. of Survey
Downstream
Length Surveyed
57.8 ft.
Total Length
57.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 18 0744 to 18 0743
MH: 18 0744MH: 18 0743downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 07449.9 ft. MGO - General Observation - MAGNEZIUM H.O COATING start9.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start55.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish55.4 ft. MGO - General Observation - MAGNEZIUM H.O COATING finish57.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0743

Observation photos (1)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    9.9 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
55.3SAV
0MWL
9.9MGOMAGNEZIUM H.O COATING start
9.9SAV
55.4MGOMAGNEZIUM H.O COATING finish
0MWM
57.8AMH18 0743
0AMH18 0744

Properties (3)

custom_field_two
4
customer
LACSD
datetime
2018-05-10T00:14:20-07:00