Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2018, 09:10 AM
  • C 0414_C 0208_6112018_044116.mp4

Date
06/11/2018
W/O
0706820
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00124
PipeID
P09600
Time
2:10 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0889
Sewer Name
C JOINT OUTFALL C - UNIT 3E
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
19
Purpose
Capital Improvement Program Assesment
Project
20180611MDM_JOINT_OUTFALL_C_UNIT_3E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
C 0414
Downstream MH
C 0208
Dir. of Survey
Downstream
Length Surveyed
244.8 ft.
Total Length
244.8 ft.
Structural Index
2
Structural Quick
3324
Structural Rating
17
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
17
Pipe schematic from manhole C 0414 to C 0208
MH: C 0414MH: C 0208downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:40AM0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - MAG COAT 70% START28.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRERTE UNDER MAG COAT56.1 ft. SSS - Surface Spalling, from 01 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE66.3 ft. SSS - Surface Spalling, from 10 to 11 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE70.8 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC75.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC156.5 ft. SAV - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG244.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC244.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE244.2 ft. MGO - General Observation - MAG COAT 70%244.8 ft. AMH - Downstream Manhole, Survey Ends - 5:10AM

Observation photos (8)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    0.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - MAG COAT 70% START

    2 ft. - General Observation - MAG COAT 70% START

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRERTE UNDER MAG COAT

    28.3 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRERTE UNDER MAG COAT

  • Surface Spalling, from 01 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    56.1 ft. - Surface Spalling, from 01 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Spalling, from 10 to 11 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    66.3 ft. - Surface Spalling, from 10 to 11 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    70.8 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    75.3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG

    156.5 ft. - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (16)

DistanceCodeObservation
28.3SSSBLISTERING PEELING CONCRERTE UNDER MAG COAT
0AMH4:40AM
75.3SAVSEVERE AGG SPORATIC
66.3SSSBLISTERING CONCRETE
244.2SAVSEVERE AGG SPORATIC
244.2SSSBLISTERING PEELING CONCRETE
0.1SSSBLISTERING PEELING CONCRETE
0MWM
244.8AMH5:10AM
2MGOMAG COAT 70% START
0MGOConn. @ Mh, 3 O' Clock. Active
56.1SSSPEELING CONCRETE
244.2MGOMAG COAT 70%
0MWL
70.8SAVSEVERE AGG SPORATIC
156.5SAVSEVERE AGG

Properties (4)

custom_field_three
SEVERE AGG VISIBLE SPORATIC--70% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2018-06-11T02:10:36-07:00