- Date
- 06/08/2018
- W/O
- 0706884
- Weather
- Dry
- Operator/Surveyor
- FRANKLIN
- Sewer ID
- Z00878
- PipeID
- P17760
- Time
- 9:49 AM
- Certificate
- U-415-06024039
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- I0022
- Sewer Name
- 30 SOUTH BAY CITIES MAIN TRUNK
- City
- HERMOSA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 30
- Page No.
- 04
- Purpose
- Capital Improvement Program Assesment
- Project
- 20180608DF_SOUTH_BAY_CITIES_MAIN_TRUNK
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- 30 0057
- Downstream MH
- 30 0056
- Dir. of Survey
- Downstream
- Length Surveyed
- 51 ft.
- Total Length
- 51 ft.
- Structural Index
- 3
- Structural Quick
- 5A3A
- Structural Rating
- 100
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 100
Pipe schematic from manhole 30 0057 to 30 0056 Observation photos (7)

2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 60% MAG

6.7 ft. - General Photograph

46.3 ft. - General Photograph

47.5 ft. - General Photograph