Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2018, 07:26 AM
Date
06/08/2018
W/O
0706820
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00124
PipeID
P09604
Time
12:26 AM
Certificate
U-014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0886
Sewer Name
C JOINT OUTFALL C - UNIT 3E
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20180604MDM_JOINT_OUTFALL_C_UNIT_3E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0212
Downstream MH
C 0211
Dir. of Survey
Downstream
Length Surveyed
412.7 ft.
Total Length
412.7 ft.
Structural Index
2
Structural Quick
312A
Structural Rating
23
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
25
Pipe schematic from manhole C 0212 to C 0211
MH: C 0212MH: C 0211downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES0 ft. AMH - Upstream Manhole, Survey Begins - 12:35AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 100% START 8:00 TO 4:002 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT35.3 ft. SSS - Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: NO - SWOLLEN BLISTERING CONCRETE77.6 ft. SSS - Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE100.2 ft. SSS - Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE158.3 ft. SSS - Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT185.3 ft. SSS - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - PEELING BLISTERING CONCRETE185.3 ft. SSS - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - PEELING BLISTERING CONCRETE214 ft. MGO - General Observation - MAG COAT 98% START214 ft. SSS - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE217.8 ft. SAV - Surface Aggregate Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC250.6 ft. MGO - General Observation - 100% MAG COAT START362.6 ft. MGO - General Observation - MAG COAT 98% START369.7 ft. SSS - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE398.4 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - SLUDGE412 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - SLUDGE412 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE412 ft. MGO - General Observation - MAG COAT 98% FINISH412.7 ft. AMH - Downstream Manhole, Survey Ends - 1:15AM

Observation photos (12)

  • General Observation - MAG COAT 100% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 100% START 8:00 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: NO - SWOLLEN BLISTERING CONCRETE

    35.3 ft. - Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: NO - SWOLLEN BLISTERING CONCRETE

  • Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    77.6 ft. - Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    100.2 ft. - Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT

    158.3 ft. - Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - PEELING BLISTERING CONCRETE

    185.3 ft. - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - PEELING BLISTERING CONCRETE

  • Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - PEELING BLISTERING CONCRETE

    185.3 ft. - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - PEELING BLISTERING CONCRETE

  • Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

    214 ft. - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    217.8 ft. - Surface Aggregate Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • General Observation - 100% MAG COAT START

    250.6 ft. - General Observation - 100% MAG COAT START

  • Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    369.7 ft. - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

Observations (23)

DistanceCodeObservation
185.3SSSPEELING BLISTERING CONCRETE
2MGOMAG COAT 100% START 8:00 TO 4:00
0MWM
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
0SSS
412DSZSLUDGE
369.7SSSBLISTERING CONCRETE
0AMH12:35AM
185.3SSSPEELING BLISTERING CONCRETE
77.6SSSBLISTERING CONCRETE
250.6MGO100% MAG COAT START
0MWM
362.6MGOMAG COAT 98% START
412SSSBLISTERING PEELING CONCRETE
412.7AMH1:15AM
158.3SSSPEELING CONCRETE UNDER MAG COAT
412MGOMAG COAT 98% FINISH
214MGOMAG COAT 98% START
100.2SSSBLISTERING CONCRETE
217.8SAVSEVERE AGG SPORATIC
35.3SSSSWOLLEN BLISTERING CONCRETE
398.4DSZSLUDGE
214SSSBLISTERING PEELING CONCRETE

Properties (4)

custom_field_three
BLISTERING PEELING CONCRETE-FEW SEVERE AGG-98%MAG
custom_field_two
4
customer
LACSD
datetime
2018-06-08T00:26:37-07:00