Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2018, 11:34 AM
  • C 0212A_C 0212_642018_050115.mp4

Date
06/04/2018
W/O
0706820
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00124
PipeID
P09605
Time
4:34 AM
Certificate
U-014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0879
Sewer Name
C JOINT OUTFALL C - UNIT 3E
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20180604MDM_JOINT_OUTFALL_C_UNIT_3E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0212A
Downstream MH
C 0212
Dir. of Survey
Downstream
Length Surveyed
330.8 ft.
Total Length
330.8 ft.
Structural Index
2
Structural Quick
2400
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole C 0212A to C 0212
MH: C 0212AMH: C 0212downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:05AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - HOT SEWAGE2 ft. MGO - General Observation - MAG COAT 98% START 8:00 TO 4:002 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT76.3 ft. SSS - Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE84.9 ft. SSS - Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE217.5 ft. SSS - Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE330.4 ft. MGO - General Observation - 98 % MAG COAT FINISH330.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE330.8 ft. AMH - Downstream Manhole, Survey Ends - 5:30AM

Observation photos (5)

  • General Observation - MAG COAT 98% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 98% START 8:00 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    76.3 ft. - Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    84.9 ft. - Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    217.5 ft. - Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

Observations (13)

DistanceCodeObservation
330.4MGO98 % MAG COAT FINISH
330.4SSSBLISTERING PEELING CONCRETE
217.5SSSBLISTERING PEELING CONCRETE
76.3SSSBLISTERING CONCRETE
2MGOMAG COAT 98% START 8:00 TO 4:00
0AMH5:05AM
0MWM
0MGOConn. @ Mh, 9 O' Clock. Active
84.9SSSBLISTERING CONCRETE
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
0MWL
0MGOHOT SEWAGE
330.8AMH5:30AM

Properties (4)

custom_field_three
BLISTERING PEELING CONCRETE- 98% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2018-06-04T04:34:08-07:00