Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 7, 2018, 07:53 AM
  • 02 0012_02 0011_672018_015413.mp4

Date
06/07/2018
W/O
0706686
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00234
PipeID
P03038
Time
12:53 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0885
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Maintenance Related
Project
20180601MDM_ARTESIA_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0011
Downstream MH
02 0012
Dir. of Survey
Upstream
Length Surveyed
393.7 ft.
Total Length
393.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 0011 to 02 0012
MH: 02 0011MH: 02 0012upstream0 ft. AMH - Upstream Manhole, Survey Ends - 2:15AM0.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. ACTIVE0.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active48.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped88.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open209.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open246.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped334.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open365.5 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES365.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active392.7 ft. MGO - General Observation - PIPE PIECE FOUND MH#11(2" THICK393.7 ft. MWM - Water Mark, 30 %of cross sectional area393.7 ft. MWL - Water Level, 10 %of cross sectional area393.7 ft. AMH - Downstream Manhole, Survey Begins - 1:55AM

Observation photos (2)

  • General Observation - PIPE PIECE FOUND MH#11(2" THICK

    1 ft. - General Observation - PIPE PIECE FOUND MH#11(2" THICK

  • Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES

    28.2 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
28.2DAGS
393.2MGOConn. @ Mh, 9 O' Clock. ACTIVE
184.2TFOpen
393.7AMH2:15AM
59.1TFOpen
0MWM
147.5TFCCapped
345.2TFCCapped
0MWL
28.2TFActive
1MGOPIPE PIECE FOUND MH#11(2" THICK
0AMH1:55AM
393.2MGOConn. @ Mh, 3 O' Clock. Active
305.6TFOpen

Properties (3)

additional_info
LARGE PIECE BROKEN PIPE FOUND DOWNSTREAM--REVERSE INSPECTION
customer
LACSD
datetime
2018-06-07T00:53:55-07:00