Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 16, 2018, 06:44 PM
  • B 0008_B 0007_16052018_120244.mp4

Date
05/16/2018
W/O
701684
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00072
PipeID
P08518
Time
11:44 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5670
Sewer Name
B JOINT OUTFALL B - UNIT 1A
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
17
Purpose
Routine Assessment
Project
WO_701684_TV30071_MAY2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
144 in.
Width
144 in.
Upstream MH
B 0008
Downstream MH
B 0007
Dir. of Survey
Downstream
Length Surveyed
236.1 ft.
Total Length
236.1 ft.
Structural Index
4
Structural Quick
5I3J
Structural Rating
411
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
411
Pipe schematic from manhole B 0008 to B 0007
MH: B 0008MH: B 0007downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 00080 ft. MWM - Water Mark, 30 %of cross sectional area2.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start48.7 ft. SRP - Surface Reinforcement Projecting, at 12 o'clock, within 8 inches of joint: NO89.6 ft. SRP - Surface Reinforcement Projecting, at 01 o'clock, within 8 inches of joint: NO196.3 ft. SRP - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start234.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"234.6 ft. SMW - Surface Missing Wall, from 01 to 05 o'clock, within 8 inches of joint: NO236.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish236.1 ft. SRP - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish236.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish236.1 ft. MSA - Survey Abandoned - CAM BLKD BY REBAR

Observation photos (6)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Projecting, at 12 o'clock, within 8 inches of joint: NO

    48.7 ft. - Surface Reinforcement Projecting, at 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Projecting, at 01 o'clock, within 8 inches of joint: NO

    89.6 ft. - Surface Reinforcement Projecting, at 01 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    196.3 ft. - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Missing Wall, from 01 to 05 o'clock, within 8 inches of joint: NO

    234.6 ft. - Surface Missing Wall, from 01 to 05 o'clock, within 8 inches of joint: NO

Observations (15)

DistanceCodeObservation
2.1SRV
2.1MGOMAG COAT
236.1SAP
234.6TFA
236.1SRP
48.7SRP
234.6SMW
0MWL
0AMHB 0008
196.3SRP
236.1SRV
0MWM
236.1MSACAM BLKD BY REBAR
2.1SAP
89.6SRP

Properties (5)

additional_info
SC359328
custom_field_two
5
customer
LACSD
datetime
2018-05-16T11:44:43-07:00
year_laid
36930