Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2018, 06:02 AM
  • 18 0283_18 0282 _17052018_232324.mp4

Date
05/17/2018
W/O
701652
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00702
PipeID
P14111
Time
11:02 PM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5613
Sewer Name
18 SHOEMAKER AVENUE TRUNK
City
NORWALK, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
WO_701652_TV18178_MAY2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0283
Downstream MH
18 0282
Dir. of Survey
Downstream
Length Surveyed
356.8 ft.
Total Length
356.8 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
210
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
212
Pipe schematic from manhole 18 0283 to 18 0282
MH: 18 0283MH: 18 0282downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 02830 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. MGO - General Observation - MAGNESIUM H.O. START53.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"56 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"101.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"103.4 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 04 o'clock, , within 8 inches of joint: YES - STICK104.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"153.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"156.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"204.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"207.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"253.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"256.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"305 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"308 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"354.4 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH354.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish356.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0282

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAGNESIUM H.O. START

    2.3 ft. - General Observation - MAGNESIUM H.O. START

  • Deposits Settled Other,  5 %of cross sectional area, at 04 o'clock,  , within 8 inches of joint: YES - STICK

    103.4 ft. - Deposits Settled Other, 5 %of cross sectional area, at 04 o'clock, , within 8 inches of joint: YES - STICK

Observations (23)

DistanceCodeObservation
0AMH18 0283
305TFC
253.2TFC
356.8AMH18 0282
104.6TFC
204.6TFC
354.4MGOMAGNEZIUM H.O. FINISH
103.4DSZSTICK
56TFC
2.3SAV
2.3MGOMAGNESIUM H.O. START
101.4TFC
207.8TFC
308TF
156.2TFC
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK
256.3TFC
53.1TFC
153.3TFC
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK
354.4SAV

Properties (4)

additional_info
SC359168
custom_field_two
3
customer
LACSD
datetime
2018-05-17T23:02:45-07:00