Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2018, 05:45 AM
  • 02 1392_02 1391 _08052018_230706.mp4

Date
05/08/2018
W/O
701119
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02963
Time
10:45 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5661
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
WO_701119_TV02220_MAY2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
02 1392
Downstream MH
02 1391
Dir. of Survey
Downstream
Length Surveyed
605.3 ft.
Total Length
605.3 ft.
Structural Index
4
Structural Quick
5V3W
Structural Rating
940
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
940
Pipe schematic from manhole 02 1392 to 02 1391
MH: 02 1392MH: 02 1391downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13923 ft. MGO - General Observation - MAG COAT6.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SPORATIC601.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish605.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1391605.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SPORATIC

    23.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SPORATIC

Observations (9)

DistanceCodeObservation
6.6SAP
605.3AMH02 1391
605.3SAP
3MGOMAG COAT
0MWM
601.5SRV
23.2SRVSPORATIC
0MWL
0AMH02 1392

Properties (4)

additional_info
SC359317
custom_field_two
2
customer
LACSD
datetime
2018-05-08T22:45:43-07:00