Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2018, 08:17 AM
  • 02 1402_02 1401_09052018_013425.mp4

Date
05/09/2018
W/O
701119
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02973
Time
1:17 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5661
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
WO_701119_TV02220_MAY2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
02 1402
Downstream MH
02 1401
Dir. of Survey
Downstream
Length Surveyed
366 ft.
Total Length
366 ft.
Structural Index
4
Structural Quick
5N3O
Structural Rating
611
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
611
Pipe schematic from manhole 02 1402 to 02 1401
MH: 02 1402MH: 02 1401downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 14020 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.6 ft. SRP - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start77 ft. SRP - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish283.5 ft. SRP - Surface Reinforcement Projecting, from 09 to 12 o'clock, within 8 inches of joint: NO333.3 ft. SRP - Surface Reinforcement Projecting, from 09 to 02 o'clock, within 8 inches of joint: NO366 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish366 ft. AMH - Downstream Manhole, Survey Ends - 02 1401366 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    39.6 ft. - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Projecting, from 09 to 12 o'clock, within 8 inches of joint: NO

    283.5 ft. - Surface Reinforcement Projecting, from 09 to 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Projecting, from 09 to 02 o'clock, within 8 inches of joint: NO

    333.3 ft. - Surface Reinforcement Projecting, from 09 to 02 o'clock, within 8 inches of joint: NO

Observations (13)

DistanceCodeObservation
366SAP
39.6SRP
366AMH02 1401
0AMH02 1402
2.1SRV
0MWL
77SRP
366SRV
2.1MGOMAG COAT
0MWM
283.5SRP
2.1SAP
333.3SRP

Properties (4)

additional_info
SC359317
custom_field_two
2
customer
LACSD
datetime
2018-05-09T01:17:56-07:00