Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2018, 07:00 AM
  • 02 1395_02 1394 _09052018_002137.mp4

Date
05/09/2018
W/O
701119
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02966
Time
12:00 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5661
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
WO_701119_TV02220_MAY2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
02 1395
Downstream MH
02 1394
Dir. of Survey
Downstream
Length Surveyed
938.2 ft.
Total Length
938.2 ft.
Structural Index
4
Structural Quick
5a3d
Structural Rating
1401
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
1401
Pipe schematic from manhole 02 1395 to 02 1394
MH: 02 1395MH: 02 1394downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13950 ft. MWM - Water Mark, 20 %of cross sectional area2.1 ft. MGO - General Observation - 95% MAG COAT INTACT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start99.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SPORATIC938.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish938.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1394938.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SPORATIC

    99.5 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SPORATIC

Observations (9)

DistanceCodeObservation
0MWL
938.2SRV
938.2AMH02 1394
2.1MGO95% MAG COAT INTACT
99.5SRVSPORATIC
938.2SAP
0AMH02 1395
0MWM
2.1SAP

Properties (4)

additional_info
SC359317
custom_field_two
2
customer
LACSD
datetime